
McLARNEY RESOURCE LIBRARY
ELECTRICAL INFORMATION
1. Convert Watts to AMPS:
·
Watts divided by
Voltage
Example:
2,300
WATTS = 2300w divided by 120v = 19.1 AMPS
(for 3 Phase divide by 1.73)
2. Convert AMPS to Watts:
·
AMPS multiplied by
Voltage
Example:
19.1 AMPS multiplied by 120v = 2300 Watts
(for 3
phase multiply by 1.73)
3. Convert Horse Power to AMPS:
·
Multiply Horse Power
by 746w (1 HP = 746 Watts)
Find
Circuit Voltage and Phase
Example:
30 HP at 480 (3 Phase) - 746
multiplied by 30 = 22380
22380
divided by 480 (3 Phase) = 46.5
46.5
divided by 1.73 = 29.5AMPS
Multiply
all the motor loads by 1.50% and go to the next circuit size.
4. Convert KVA to AMPS:
·
Multiply KVA by
1000/voltage
Example:
30 KVA
multiplied by 1000v = 30,000 Watts
30,000
Watts divided by 480 = 62.5 AMPS
(for 3
phase divide by 1.73)
5. Convert KW to AMPS:
·
Multiply KW by
1000/voltage and then by power factor
Example:
30KW multiplied by
1000v = 30,000
30,000 divided by
480 = 62.5 x .90 = 56.25amps
(for 3
phase divide by 1.73)
6.
Building Supply Power:
·
Large buildings
generally have 277/480v.3ph.4w incoming power to a main disconnect. This is fed by the power company. Most lighting, air conditioning and
equipment are fed by this voltage. To
feed general receptacles a step-down transformer is installed (480v 3PH. Input
and 120/208V/.3PH Output).
7. Panelboard Capacity
·
100A panelboard will
handle 100A per phase
·
Find the existing
loads from each circuit
·
Add them and multiply
by the Circuit Voltage
·
Divide by panel
voltage and (1.73 for 3 Phase)
·
The total should not
exceed 80% of the 100A
·
Remember Circuit Voltage is not the same as Panelboard
Voltage.
·
Panelboard Voltage
208v or 480v
·
Circuit Voltage might
be 120v or 277v
8.
Portable Equipment:
·
Portable equipment cannot
be hardwired (this includes benches that are not fastened to the floor)
·
Typical solution is
to install a cord drop or a cord with a plug
9. Safety Disconnect:
·
A circuit disconnect
must be installed within sight or not more than 50ft. from the piece of
equipment
10. Breaker Style and Brand:
·
When a new breaker is
installed in an existing panelboard, verify that the proposed breaker style is
listed on the panelboard manufacturer’s name card (information posted on the
panelboard cover)
·
The AIC Rating of the breaker must be equal or greater than
the panelboard’s AIC rating (located on the information card)
11. Clearances:
·
All electrical
panelboards, transformers, switchboards, disconnects, etc., must have the
following working clearances:
·
42” for 480v
equipment
·
36” for 240v
equipment
12. Circuit Identification:
Even
though it is not a code issue, it still is a good practice to –
·
Require that all
receptacles, light switches, and electrical equipment be labeled with the
circuit information, including the panelboard designation and circuit number
13. Amount of Devices Per Circuit:
·
Receptacles (Rule of Thumb):
Not more than (6) per
circuit
·
Copiers and
appliances (coffee pots, microwaves. refrigerators, water coolers, etc.) should
be on a dedicated circuit
·
Dedicated means no
other load or device should be connected to this circuit
14. Light Fixtures Per Circuit:
·
Multiply ballast AMPS
by the amount of ballast or lamp watts
·
The total should not
exceed 80% of the Circuit AMPS
Example
A 20AMP 120v circuit could only
be loaded to 16 AMPS which equals 57 fluorescent lamps-34 Watt or 19 2 x 4
Fluorescent Fixtures-3lamp.
15. Device Mounting Heights:
·
Receptacles 15”
·
Receptacle in
bathroom 44”
·
Receptacle above
counter 4” above back splash
·
All heights are the
center line of the device and above finished floor or surface.
·
Light switches 46”
·
Restroom light
switches 42”
·
Disconnects and
panelboards should not be more than 6’ from the finished floor to the top of it
16.
Required GFI Protection:
·
All receptacles
within 6’ of any water source
·
Receptacles on the
roof
·
Receptacles exposed
to the outside weather and in wet locations must be GFCI protected. This can be accomplished by installing an
approved GFI breaker or a receptacle with built-in GFI protection.
17. New
Building Electrical Services Protected by Main GFI Breaker:
·
All electrical
services 1000AMPS at 480v or greater must be protected by a GFI (Ground Fault
Interrupter) main breaker
·
Ground fault testing
must be performed by an approved testing agent. A ground neutral could cause
the main GFI breaker to trip
·
A short circuit on a
lighting circuit could cause the main circuit breaker to trip which would
result in the entire building being shutdown until the beaker is restored to
the ON position
18. Isolated Ground Receptacle:
·
All critical computer
equipment and some copiers should be connected to an isolated ground
receptacle(commonly orange color)
19. Server, Telephone and Data Rooms:
·
All circuits feeding
these rooms should not be shared with other devices that are not part of these
rooms
·
An overload on a
circuit caused by someone plugging in a piece of equipment into a receptacle
that is connected to the same circuit as these rooms will trip the breaker and
data loss or hardware damage could occur
20. Energy management Systems:
·
Typical Energy
Management System controls the light fixtures per title 24, automatic lighting
control should be in 5,000sf increments (maximum) in a building on the
following schedules:
·
Lights on at 6:00
a.m.
·
Lights off at 6:00
p.m.
·
Off every 2 hours
thereafter during week days if overridden
Saturday,
Sunday and Holidays - off all day
Saturday,
Sunday and Holidays - off every 2 hours thereafter if overridden
21.
Outside Lighting Controls:
·
Outside lighting is
normally controlled by a timer and a photo cell
·
The timer is
typically located in the main electrical room or electrical closet
·
The photo cell is
typically located on the roof
·
Some building outside
lights are controlled by a photo cell.
If lights remain on during the day, the photo cell is not functioning
and requires replacement.
The foregoing
guidelines are given for guidance purposes only. Please consult your electrical contractor.
UPDATE 6/99
